Electrical Considerations
The Zone Monitor with Isolator is loop powered and operates at 17-28V DC with protocol pulses of 5-9V.
Mechanical Construction
The Zone Monitor with Isolator is supplied with a backbox for surface mounting, and is for indoor use only. Two LEDs, one red and one yellow, are visible through the front cover of the enclosure. The red LED is illuminated to indicate that a fire alarm condition has been detected on the zone wiring. The yellow LED is illuminated whenever the built-in isolator has sensed a short circuit loop fault. The backbox is a polycarbonate moulding.
Backward Compatibility
The Zone Monitor with Isolator operates only with control equipment using the Apollo XP95 or Discovery protocol.
Product Information
The Zone Monitor powers and controls the operation of a zone of up to 20 Apollo Series 65 or Orbis Fire Detectors from a Discovery or XP95 loop.
Key Features
fitted with a bi-directional short circuit isolator unaffected by loop short circuits